ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
39
997-457-000-8, Issue 8
January 2010
1
The Language screen is displayed first.
2
Press the ‘
2
/
8
’ buttons to step through the Panel
Options menus until the Control Keys screen is displayed.
3
Press the ‘
6
’ button to change the setting to level 1
(no passcode) or level 2 (user passcode). The default
access level is level 2.
4
Press ‘
4
’ to return to the Setup menu. All changes
will be saved on exiting.
5.5.1.4 LED 1H Mode
The default function of this LED is PLANT ALARM. This
option allows the LED to be configured as FAULT O/P:
FAULT/DISABLED.
1
From the Setup menu screen, using the numeric
keypad press the ‘
1
’ button to enter the Panel
Options menu. The Language screen is displayed first.
2
Press the ‘
2
/
8
’ buttons to step through the Panel
Options menus until the LED 1H Mode screen is
displayed.
3
Press the ‘
6
’ button to toggle the LED function.
4
Press ‘
4
’ to return to the Setup menu screen. All
changes will be saved on exiting.
5.5.1.5 LED 2C Mode
The default function for this LED is PRE-ALARM. This
option allows this LED on panels with the new 5-button
membrane to be configured as SOUNDERS SILENCED.
1
From the Setup menu, using the numeric keypad press
the ‘
1
’ button to enter the Panel Options menu. The
[Setup]
Control Keys Access Level = 2
> : Change
¦
: More
< : Exit
[Setup] Language =
English
> : Change
¦
: More
< : Exit
or
8
2
EN54-2 : 8.2.4 g)
If a fault-routing output is
configured, a fault-routing
output transmission circuit
fault indication must be
provided.
PLANT ALARM
FAULT O/P: FAULT / DISABLED
DISABLEMENT
FAULT
TEST
POWER SUPPLY FAULT
EARTH FAULT
POWER
FIRE OUTPUT ACTIVE
DELAYS ACTIVE
FIRE OUTPUT: FAULT / DISABLED
FIRE CONTROL O/P: FAULT / DISABLED
PRE- ALARM
SYSTEM FAULT
SOUNDER: FAULT / DISABLED
[Setup] Language =
English
> : Change
¦
: More
< : Exit
[Setup]
LED 1H =
Plant Alarm
> : Change
¦
: More
< : Exit
[Setup]
LED 1H =
Fault Output: F/D
> : Change
¦
: More
< : Exit
1
or
8
2
6
[S1
Setup]
4: Peripheral Options
5: Day / Night Settings
¦
: More
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
¦
: More
DISABLEMENT
FAULT
TEST
POWER SUPPLY FAULT
EARTH FAULT
POWER
PLANT ALARM
FIRE OUTPUT ACTIVE
DELAYS ACTIVE
FIRE OUTPUT: FAULT / DISABLED
FIRE CONTROL O/P: FAULT / DISABLED
PRE- ALARM
SYSTEM FAULT
SOUNDER: FAULT / DISABLED
SOUNDERS SILENCED