ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
65
997-457-000-8, Issue 8
January 2010
[Sensor]
Enter Address ____
5.6 Circuit Options
The Circuit options menu offers the facility to individually
auto-configure, manually learn or view the following circuits:
a. Signalling Line Circuit - SLC (loop)
b. On-Board Output Circuits - including sounder, control
and relay circuits.
To select the Circuit options menu:
1
From the Commissioning menu, press the ‘
2
’ button
on the numeric keypad to access the Circuit option menu.
2
The LCD displays the Circuit options available.
3
Select the number corresponding to the type of circuit
that requires changing, i.e. ‘
1
’ for the SLC Loop, or
‘
2
’ for On-Board.
The LCD then displays the appropriate Circuit menu
display.
5.6.1 Signalling Line Circuit (SLC) - Devices
This option enables the manual configuration of devices
to a pre-configured analogue addressable SLC loop.
To manually learn devices on the SLC loop:
1
From the Circuit menu, below, using the numeric
keypad press ‘
1
’ to select the SLC loop configuration.
2
The LCD displays the Devices and the Learn options. Using
the numeric keypad, press ‘
1
’ to select the Devices menu.
3
Select a device option by using the numeric keypad and
pressing ‘
1
’ to configure sensors or ‘
2
’ to configure
modules (see
Input Modules
and
Output Modules
overleaf).
4
At the prompt, using the numeric keypad enter an
address number and confirm using the ‘
5
’ button.
When the required device address has been entered,
the LCD shows the current settings and the available
editing functions.
[S1 COMM]
1 : Setup
2 : Circuit
3 : CBE Rules
4 : Zones 5 : Access
¦
: More
[S1 Circuit]
1 : SLC Loop 2 : On-Board
[S1 Circuit]
1 : SLC Loop 2 : On-Board
[S1 SLC]
1 : Devices
2 : Learn
[S1 Device]
1 : Sensors
2 : Modules
2
1
1