ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 2 - VIEW
, Optiplex & SMART Sensors
A2 - 4
997-457-000-8, Issue 8
January 2010
A2.2 Learning Individual VIEW
TM
Sensors
When installed on a loop from the ID61/62 Panel, each
VIEW
TM
sensor is assigned the Advanced VIEW
TM
Sensor
(AVS) type by default. This may then be configured as
Advanced VIEW
TM
Reference (AVR) type.
A VIEW
TM
sensor may be learnt in the same manner as
any sensor but has an additional ‘Type’ configuration
option. The procedure to configure the sensor type is as
follows:
1
Using the numeric keypad, press ‘
1
’ to select the
sensors configuration option.
2
At the prompt, using the numeric keypad enter the
address of the VIEW
TM
sensor to be edited and confirm
using ‘
5
’.
3
The LCD then shows current settings and editable
parameters. Using the numeric keypad, press ‘
2
’ to
select the ‘Type’ option.
Note:
Use ‘
2
/
8
’ to select the next/previous address
respectively.
4
The LCD then displays the VIEW
TM
device type
selection menu. Using the numeric keypad, press ‘
1
’
or ‘
2
’ to select the ‘AVS’ or ‘AVR’ type respectively.
The display automatically returns to the previous
menu, as shown below:
[S1 Device]
1 : Sensors
2 : Modules
[Sensor nn - AVS] 1 : Zone (nn)
2 : Type
3 : Sensitivity
4 : [
Blank/Existing Text
]
[Sensor]
Enter Address ____
[Sensor nn - AVR] 1 : Zone (nn)
2 : Type
3 : Sensitivity
4 : [
Blank/Existing Text
]
[Sensor nn - AVS]
Select Type :
1 : AVS
2 : AVR
< : Cancel
1
2
or
1
2