ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
70
997-457-000-8, Issue 8
January 2010
5.6.1.3 Type Setting
Standard input modules in zones 1 to 16 can be assigned
to various types as shown below. A Manual Call Point (MCP)
input has the action of a zone fire alarm ‘Manual Call Point’
with prioritized polling. A Fire Alarm Monitor (MON) input
has the action of a zone fire alarm with non-prioritized polling.
An input module assigned to a zone in the range 17 to 32 is
automatically given the type AUX, for a plant alarm input.
Input devices of type AUX can be programmed for plant
alarm, reset panel, silence sounders, mute buzzer, class
change, (only used when Class Change input has been
configured for Day Mode start), abort switch, hold switch,
Extinguishing System released and Extinguishing System
fault (the last four cases are functions associated with
the configuration of Extinguishing System inputs).
The device type is configured during the learn process.
Sensor types and Plant Warning inputs (AUX) cannot be
changed. The ‘Type’ menu option is not shown on the
display for these devices.
Monitored output modules can be assigned to various
types as shown below.
To change the module type as displayed on the LCD:
1
Using the numeric keypad press ‘
2
’ (Type option)
from the menu displaying the module attributes:
2
Selecting the Type option displays one of the following:
Note:
On-Board circuits 1, 2, 3 and 4 support SDR, SDH,
RLY
1
, CTL, TxD
2
, RLE
1
, CTE, EST
1
, ESO and ESE
1
Output Circuits. On-Board circuits 5 and 6 are fixed
as Unmonitored -VE Output circuits.
3
Select the module type using the press the ‘
2
/
8
’
buttons to cycle through the list of modules and select
the new type. The LCD then displays the new module
attributes menu. A typical menu is shown below:
2
EN 54-2 : 7.6.1, 7.8
Level 2 Keyswitch access
MUST be used with an input
Type AUX panel Reset (7.6.1)
& Silence/Resound (7.8).
The first 30 modules (from
lowest address upwards)
restricted to types MCP, DKM,
MRL, IRL and all AUX actions
except Plant Alarm, are added
automatically to a priority poll
list. Subsequent modules are
polled normally.
[Module nn - MCP] 1 : Zone (nn)
2 : Type
3 : CBE Rule (nn)
4 : [ Blank/Existing Text
]
2
8
or
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
1
Non-monitored outputs
2
If ‘TxD’ is selected refer to the
Operating
Manual, Section 4.12.7 Voltages - User
Option
to set the transmission circuit
reference impedance to enable correct
fault monitoring.
[Module nn - MCP] Select Type :
>MCP< DKM MON MNS MRL IRL
<: Cancel
[Module nn - ZMX] Select Type :
>ZMX< FRM
<: Cancel
[Module nn - SDR] Select Type :
>SDR< CTL RLY EST ESO ESM TxD ESE RLE CTE S
[Module nn - MCP] 1 : Zone (nn)
2 : Type
4 : [
Blank/Existing Text
]
[Module nn - SDR] 1 : Zone (nn)
2 : Type
3 : CBE Rule (nn) 4 : [
Blank/Existing Text
]