2.6 Assembling the Panel
With the back box secured to the wall and all external cabling
ready for termination, assemble the panel as follows:
1
Ensure that all power to the panel is isolated and
observe ALL safety and
anti-static precautions
when
installing the PCB assembly.
2
Taking suitable anti-static precautions, offer the four slotted
holes of the chassis to the back box and, with it adequately
supported, connect the chassis earth lead to the earth blade
connectors in the back box.
3
Locate the back box on the M4 SEM screws. Once in position,
use a cross-headed screwdriver to tighten the screws.
4
Fit the labels. They may require the application of a
low tack adhesive:
i
Apply low tack adhesive to hatched area indicated.
ii Slide each label into position.
iii Apply slight pressure to the area along the bottom
edge of the fascia to ensure the labels are secure.
5
Insert the IEC mains plug into the socket on the top of
the PSU and apply mains power supply - then connect
the batteries. Check the PCB assembly operates
correctly and then
isolate all power
to the panel.
6
At the Main PCB assembly:
i
Noting the cable polarity, connect all cables and
secure at the correct termination blocks, see
Cables
& Wiring
below.
ii Set all required hardware jumper configurations,
refer to the
Section 4 Commissioning
.
7
Fit the RS485 Interface Module PCB, if applicable, refer to
Section 2.7 RS485 Communications Link
.
8
Re-apply the mains power supply and then connect
the batteries.
9
Disconnect the links at the earth fault monitoring jumper
E_FLT (JP6) and configuration lock MEM (JP7). Then
connect the RS232 9-way ‘D’ type Data Transfer Lead
(PN 082-173) to the panel at the RS232 socket
connector, SK3. Using the Support Tool, transmit the
latest system configuration to the panel.
10
Remove the lead and fit the links at JP6 and JP7, then
fit the cover.
Note:
Connect the earth wire to the inner side wall of the
cover at the tag marked with the earth symbol.
Cables & Wiring
i
ÜE/Sounder Output A and Sounder Output B (TB1)
ii
CFG Outputs C and D (TB2)
iii Digital / ÜE Inputs (TB3)
iv 24 V Auxiliary Power Supply (TB4)
v
Loop Cable Output/Input (TB5)
vi -VE Outputs (TB6)
vii Keyswitch
viii PSU Input (SK4, SK5)
ix FBF Communications Cable (TB9)
x
FBF Power Supply (TB8)
xi RS232 Port (printer option)
xii RS485 Communications Cable (SK1).
0
0..9
3
1
2
4
6
7
5
[
9
8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
124-391 ID50+ PCB
CRYSTAL
FREQUENCY (XT2)
i
xi
xii
x
ix
viii
viii
vii
ii
iii
iv
v
vi
1
1 & 5
1 & 5
2
7
TEMP
SNSR
+
-
4
JP6
E_FLT
JP6
E_FLT
JP7
MEM
JP7
MEM
9
9
8