Appendix 4 - EN54-2 Options with Requirement
s
A4 - 3
997-457-000-8, Issue 8
January 2010
ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
A12 Fire Alarm Device(s)
This is also a VdS 2540 requirement. To satisfy the
requirements of EN54-2 7.8 the CIE is provided with the
required access level 2 controls. Refer to Section
4.5
SILENCE / RESOUND Pushbutton
of the ID61/62
Operating Manual for more details.
A13 Fire Alarm Routing Equipment (7.9.1)
This is also a VdS 2540 requirement. The CIE allows
this EN54-2 option to be configured.
A dedicated fire output (transfer) relay is provided by the
CIE. In addition, the internal sounder/relay circuits are
configurable as remote fire outputs. The CIE provides an
LED to indicate when the fire relay or any configured remote
fire outputs are active. Refer to
Section 4.4.5 Configuration
Outputs C and D
and
Section 5.6.3 On-board Circuits
for more details.
A14 Fire Alarm Routing Equipment with Alarm
Confirmation (7.9.2)
This is also a VdS 2540 requirement. The CIE allows
this EN54-2 option to be configured.
The CIE allows a remote fire output (transfer) to be
configured. In addition, a fire output active condition, using
a return signal from the remote fire signal routing
equipment, can be configured using one of the provided
digital input circuits. With the panel function set to VdS
mode activation of a fire alarm routing equipment return
signal drives this indicator.
Refer to
Section 4.4.5 Configuration Outputs C and D
and
Section 5.6.3 On-board Circuits
for more details
on setting up the fire routing output. The feedback signal
is connected to the on-board digital input 2.
A15 Automatic Fire Protection: Type A
This is an optional VdS 2540 requirement. The CIE allows
the configuration of an output to fire protection equipment
using an output module. Refer to
Section 5.6.1
Signalling Line Circuit (SLC)
- Devices for more details.
A16 Automatic Fire Protection: Type B
This is an optional VdS 2540 requirement. The CIE does
not allow this option to be configured.
A17 Automatic Fire Protection: Type C
This is an optional VdS 2540 requirement. The CIE allows
the configuration of an output to fire protection equipment,
together with associated feedback signals, using a M221-SI
loop module, located internally. An Extinguishing System
(SST) display unit is also required. More details can be found
in documents 997-581-000-1 (Installing the M221-SI Module)
and 997-580-000-1 (Installing the NF-SST Display Box).