ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
87
997-457-000-8, Issue 8
January 2010
5.7.8 Zones
The Zones option determines the output response when
a zone detects an alarm. Each zone can be configured
as Yes (Y), No (N), Pulse (P), Coincidence (C) or Delay
(D) - see
Section 5.7
for definitions of these parameters.
If Day Mode is enabled (Section 5.5.5.1, Day Mode
Activity) delays do NOT occur unless manually activated.
Manual activation can occur at any time of day - it does
not have to be during the set Day Mode period. Delays
are automatically de-activated with the end of the day
mode period.
To change the CBE Rules: Zone Setting from the CBE
Rules: Output menu, follow the described procedure
below:
1
From the menu options below, press the ‘
9
’ button
to select the Zones option.
2
The LCD displays the pattern number and zone range
(either 1 to 16 for fire alarms or 17 to 32 for plant
alarms) on line 1. Line 2 of the LCD displays the
selected zone’s number, the full description of its
current status and the zone’s flashing editable status.
To select a zone, press the ‘
6
’ button until the
appropriate zone number appears on line 2 in the
left-hand corner. The display cycles from 16 to 1 and
32 to 17.
3
To change a zone’s status, press the ‘
2
/
8
’ buttons
until the required state is displayed.
4
Confirm the changes by pressing the ‘
5
’ button.
Press ‘
4
’ to cancel any changes.
CBE Rule:01
6:Class Change
7:Two Zone
9:Zones
¦
: More
CBE Rule 01 Zones
1 - - - - - - - - - - - - - - - - - - - - 1 6
[Zone 01]
[Yes
]
Y
YYYNYYYNDDNCCNN
CBE Rule 01 Zones
1 - - - - - - - - - - - - - - - - - - - - 1 6
[Zone 06]
[No
] YYYYN
N
YYNDDNCCNN
CBE Rule 01 Zones
1 - - - - - - - - - - - - - - - - - - - - 1 6
[Zone 06]
[No
] YYYYN
N
YYNDDNCCNN
CBE Rule 01 Zones
1 - - - - - - - - - - - - - - - - - - - - 1 6
[Zone 06]
[Yes
] YYYYN
Y
YYNDDNCCNN
CBE Rule 01 Zones
1 - - - - - - - - - - - - - - - - - - - - 1 6
[Zone 06]
[Pulse
] YYYYN
P
YYNDDNCCNN
6
2
8
x5
9