ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Inst
allation Guide - Cabling
19
997-457-000-8, Issue 8
January 2010
3.1.1 Cable Terminations
This section provides guidance on where to bring cables
into the back box for ease of termination:
a. The mains supply should be brought into the control
panel such that the cable path to the mains termination
block is kept as short as possible.
b. All loop and ancillary cable terminations should be
brought into the panel at suitable positions to ensure
tails are kept as short as possible.
The drawings below show recommended points of entry
so that cabling can meet these requirements.
Knockout/
Termination Point
Cable Type
a
RS485 Communications
b
Sounder/ÜE Output A and
Sounder Output B
c
Sounder/VFC Outputs C
and D
d
Digital Input 1 and Digital
Input 2 (ÜE return, not
supported)
e
DC Auxiliary Supply
f
Loop Out, Loop In
(return)
g
-VE Outputs 1 and 2
h
FBF Connections
(Not supported)
i
Mains power supply.
Note:
The FBF Signal and Power supply
cables (h) and Digital/ ÜE (d) port 2
are not supported in UK.
For specific PCB cable termination details
see
Commissioning:
Section 4.4.1, Loop Wiring,
Section 4.4.2, RS485 Communications Link,
Section 4.4.3, DC Auxiliary Output,
Section 4.4.4, Sounder Circuits Outputs A and B,
Section 4.4.5, CFG Outputs C and D,
Section 4.4.6, -VE Outputs,
Section 4.4.7, Digital / ÜE Inputs.
i
h
b
d
c
Alternative FBF (multi-wire) knockouts
Alternative FBF (multi-wire) knockouts
e
f
g
a
b
i
c d e
f
a
g
h
Avoid routing cables
through the space
required for optional
printer fitting.