ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
50
997-457-000-8, Issue 8
January 2010
pulse response. This feature is required for VdS-
compliant operation only.
5.5.3.12 Fireman’s Work Panel
This option allows the panel to be configured to work
with a German or Swiss Fireman’s Work Panel (FWP).
5.5.3.13 FWP 2 Output Activation
This option is used to control the way the Transmission
Device-triggered output, FWP 2, is activated by the
Fireman’s Work panel (FWP).
This feature is required for VdS-compliant operation only.
5.5.3.14 Double Address Detection
Automatic detection of devices with the same address is
the default condition. If this facility is not required it may
be turned off using this menu option.
1
From the Setup menu screen, press the ‘
3
’ button on
the numeric keypad to enter the Device Options menu.
The Device blinking screen is displayed first. Press the
‘
2
/
8
’ buttons to step through the Device Options
until the LCD shows the Double Address Detection
menu.
2
Press the ‘
2
/
8
’ buttons to step through the Device
Options until the LCD shows the Double Address
Deteaction menu.
3
[Setup] Double Address Detection =
OFF
> : Change
¦
: More
< : Exit
or
8
2
5.5.3.15 TD/ES Disablement at Access Level 2
The Transmission Device (TD) and Extinguishing System
(ES) outputs can be configured for automatic disablement
at access level 2 via the panel keyswitch or cover-off switch.
1
From the Setup menu screen, press the ‘
3
’ button on
the numeric keypad to enter the Device Options menu.
Press the ‘
2
/
8
’ buttons to step through the Device
Options until the LCD shows the TD/ES Auto Disable menu.
[Setup]
TD/ES Auto Disable =
No
> : Change
¦
: More
< : Exit
3
6
[Setup]
TD/ES Auto Disable =
Yes
> : Change
¦
: More
< : Exit
or
8
2
2
Press the
6
button to select the TD/ES automatic
disbablement function. Press this button again to cancel.
[Setup]
Device Blinking = ON
> : Change
¦
: More
< : Exit