ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
62
997-457-000-8, Issue 8
January 2010
6
5
5
[Setup]
Primary Delay Time = 30 Seconds
Enter new value ____
: Confirm
< : Cancel
[Setup]
Primary Delay Time = 30 Seconds
Enter new value 300
: Confirm
< : Cancel
[S1
Setup]
4: Peripheral Options
5: Day / Night Settings
¦
: More
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
¦
: More
5.5.5.4 Primary/Extend Delay Timers
The Primary Delay Timer allows an initial investigation time
of up to 300 seconds (default 30 seconds) to be entered
or changed. The Extend Delay Timer allows an additional
delay (default - 3 minutes) to be entered or changed. The
total delay time cannot exceed 10 minutes. To set delay
times:
1
From the Setup menu screen, press the ‘
5
’ button
on the numeric keypad to enter the Day/Night
Settings menu. The Day Mode Activity screen is
displayed first.
2
Pess the ‘
6
’ button. The display then prompts you
for the new value:
3
Enter the required delay time using the numeric
buttons; (e.g. to set the delay time to the maximum
value of 300 seconds, first enter ‘3’, then enter ‘0’, ‘0’).
4
Press the ‘
5
’ button to confirm and return to the
Setup menu screen.
6
Repeat steps 1 to 5 for the Extend Delay Time, using
the Extend Delay Time display and a maximum value
of 10 minutes.
5.5.5.5 Heat Det. End Delay
The Day Mode function, Delays to outputs, can be
cancelled when a heat sensor goes into alarm. To select
the Heat Det. End Delay option:
1
From the Setup menu screen, press the ‘
5
’ button
on the numeric keypad to enter the Day/Night Settings
menu. The Day Mode Activity screen is displayed first.
[S1
Setup]
4: Peripheral Options
5: Day / Night Settings
¦
: More
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
¦
: More
5
[Setup]
Day mode activity = DISABLED
> : Change
1 : Disable
¦
: More
< : Exit
[Setup]
Day mode activity = DISABLED
> : Change
1 : Disable
¦
: More
< : Exit