ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 2 - VIEW
, Optiplex & SMART Sensors
A2 - 2
997-457-000-8, Issue 8
January 2010
Non-VIEW
TM
Sensor Sensitivities
The ID61/62 panel supports co-operative multi-sensing
for sensor types other than VIEW
TM
. When configuring
ION, OPT, MLT, OPX/SM2, SM3 or SM4 sensors a third
menu option, Group, is displayed with the default group
number displayed in the brackets. A sensor may be
assigned to one of up to 50 groups and mixed with other
sensor types. Allocation to a non-zero group enables a
sensor’s inclusion in the AWACS
TM
algorithm. However,
allocation of a sensor to Group 0 excludes it from the
AWACS
TM
algorithm and the existing alarm detection
algorithm is used instead (the sensor will operate as a
stand-alone device).
Note:
When transferring a configuration from an earlier
version panel, the group number is defaulted to
‘1’. This must be changed to ‘0’ for all devices not
being monitored by the AWACS
TM
algorithm.Non-
VIEW
TM
devices learnt using software version 5.00,
or above, will default the group to ‘0’.
Alarm and pre-alarm sensitivity levels can be set in
addition to selecting a multi-sensing group.
1
To change the group, press the ‘
3
’ button on the
numeric keypad.
2
Enter a new group number, e.g. 2, and press ‘
5
’ to
confirm.
3
Using the numeric keypad, to change the alarm and/
or pre-alarm sensitivity levels press the
1
pushbutton
or to change the Day Mode sensitivity setting, press
the
2
pushbutton.
4
At the appropriate prompt enter the desired sensitivity
setting.
[Sensor nn - AAA]
Sensitivity
Enter new AWACS Group : ____
< : Cancel
[Sensor nn - AAA]
Sensitivity
1 : Alarm (L5,5)
2 : Day (L5,5)
3 : Group (0)
[Sensor nn - AAA]
Sensitivity
1 : Alarm (L5,5)
2 : Day (L5,5)
3 : Group (2)
1
3
or
2
CAUTION!
Use care when including
sensors to AWACS groups as
this may conflict with other
configured operations, such
as coincidence.