Appendix 4 - EN54-2 Options with Requirement
s
A4 - 2
997-457-000-8, Issue 8
January 2010
ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
A4 Total Loss of Power Supply
This is an optional VdS 2540 requirement. The CIE does
not allow this EN54-2 option to be configured.
A5 Delays to Outputs
This is an optional VdS 2540 requirement. The CIE allows
this EN54-2 option to be configured. Refer to
Section
5.5.5 Day/Night Settings
for more details
If an input module is used to provide a return signal from
the external system, the module must be configured as
a type MON to prevent this input overriding Day/Night
Mode switched delays.
A6 Manual or Automatic Switching of Delays to
Outputs
This is an optional VdS 2540 requirement. The CIE does
not allow this EN 54-2 option to be configured.
A7 Dependency on More Than One Alarm
Signal: Type A
This is an optional VdS 2540 requirement. The CIE does
not allow this EN 54-2 option to be configured.
A8 Dependency on More Than One Alarm
Signal: Type B
This is also a VdS 2540 requirement. For further details,
refer to
Section 5.7 Control-By-Event Output Rules
for more details on how to set up Dependencies (known
as Coincidences in the rest of this manual)
A9 Dependency on More Than One Alarm
Signal: Type C
This requirement is prohibited under VdS 2540
.
The CIE does not allow this EN54-2 option to be
configured.
A10 Disablement of Each Address Point
This is an optional VdS 2540 requirement. The CIE
complies with this EN54-2 option requirement.
Refer to
Section 4.10 DISABLE / ENABLE - User
Option
of the ID61/62 Operating Manual for more details.
A11 Test Condition
This is also a VdS 2540 requirement. The CIE complies,
using an access level 2 passcode, with this EN54-2 option
requirement. Refer to
Section 4.9 TEST - User Option
of the ID61/62 Operating Manual for more details.