5.6.1.2 Sensor Sensitivity Setting
This option allows the sensitivity of sensors to be changed
during device configuration. Access is via the Circuit menu.
Individual sensor Alarm and/or Day settings can be changed.
VIEW
TM
Sensors and SMART 4 Multi-Sensors
The
ID60
Panel supports VIEW
TM
and SMART 4. See
Appendix 2, ID60 Single Loop Panel Differences
.
Co-operative Multi-sensing Groups
The
ID61/62 Panels
supports co-operative multi-sensing
through the
A
dvance
W
arning
A
ddressable
C
ombustion
S
ensing (AWACS
TM
) software algorithm for the following
devices: VIEW
TM
, ION, OPT, MLT, OPX/SM2 (Optiplex Multi-
Sensor), SM3, SM4, (SMART 3 and 4 Multi-criteria
Sensors). Once included in the AWACS
TM
algorithm, the
sensitivity configuration follows that for VIEW
TM
device types,
i.e. using levels and not a percentage of alarm. During
configuration of the sensor sensitivity values, the LCD returns
to the previously configured value if any of the following occurs:
a. The ‘
4
’ button on the numeric keypad is pressed.
b. The panel state is unchanged for 1 minute.
c. A value outside the predefined operating limits (80% to
120%
or L1 to L6 for OPX/SM2, SM3 or SM4
) is entered.
To change the sensor sensitivity settings:
1
At the sensor attributes menu, press the ‘
3
’ button
on the numeric keypad to display the Sensor Sensitivity
Setting menu:
2
Using the numeric keypad, press ‘
1
’ to select the Alarm Sensitivity
setting or press ‘
2
’ to select the Day Mode Sensitivity setting.
3
At the appropriate prompt, use the numeric keypad to
enter the desired percentage value. Press ‘
5
’ to
confirm the value entered.
4
Press ‘
3
’ to select a new AWACS group, if required.
At the appropriate prompt, use the numeric keypad to
enter the desired AWACS group:
5
Press ‘
5
’ to confirm the AWACS group entered or
press ‘
4
’ to cancel.
1
2
or
2
1
3
[Sensor nn - AAA]
Sensitivity
1 : Alarm(100%)
2 : Day(100%) 3 : Group (00)
[Sensor nn - AAA]
Sensitivity
Enter new alarm level : 120
< : Cancel
[Sensor nn - AAA]
Sensitivity
Enter day mode alarm : 80
< : Cancel
[Sensor nn - AAA]
Sensitivity
1 : Alarm(120%)
2 : Day(80%)
< : Cancel
[Sensor nn - AAA] Sensitivity
Enter new AWACS Group : _
< : Cancel
SMART 4 Devices
The mult-criteria sensor SMART 4
logical device type, depending on loop
protocol, is SM4 (CLIP) or SMT4
(OPAL).