COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
107
954 SmartServo FlexLine
7.3.6.9 Board Commissioned Entity
The
[Board Commissioned]
entity will display either
<True>
if all
functions are commissioned or
<False>
if any of the functions are not
commissioned.
☛
If the
[Board Commissioned]
entity displays
<False>,
check each
function parameter again. Use the table from
7.3.6.8.
7.3.6.10 Fail-safe Level Application
Following steps include all commissioning-aspects settings for the Fail-
safe level application.
☛
The corresponding jumper of the concerned relay must be in the
Normally Open (NO) state (= default setting).
NOTE: In the Commissioning stage, no jumper setting can be changed
without breaking the compartment screw sealing.
☛
Set [Operation Mode] to [Alarm Mode].
☛
Set [Relay Mode] to <Energized>.
☛
Set [Alarm Mode] to [PV Monitor].
☛
Set
[Monitor Board ID]
to <board id> of product-level board.
☛
Set
[Monitor Board Instance]
to <board instance> of related product-
level board.
Set
[Monitor Function Instance]
to <function instance> of related
product-level board.
☛
Set [Monitor Source] to <PV>.
☛
Set [Monitor Mode] to [Remote].
☛
Set [Remote Threshold Source] to <HH>, <HA>, <LA>, or <LL>.
☛
Set corresponding alarm setting of the related product-level board.
☛
Set [Status Behavior] to <BAD-UNCERTAIN>
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...