COMMISSIONING
230
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name
Value Range
Default Value
Description
[Analog output
stop proof test]
Command
Terminates an active analog
output proof test. Upon
termination, the normal process
will resume and contact 2 will
close.
[Analog output
proof test
interval]
< 1 – 3650 >
(days)
< 1825 >
The maximum time interval
permitted between analog
output proof tests. If exceed
and when an analog output safe
state is not active, the analog
output safety function status will
change to W to signal a warning
that a proof test is overdue. The
status code will remain as NO
ERROR.
[Analog output
proof test
timeout]
< Auto timeout off >
< 5 minutes >
< 10 minutes >
< 20 minutes >
< 30 minutes >
< 5 minutes >
If not < Auto timeout off >, the
maximum time duration an
analog output proof test will
remain active. If exceeded the
proof test will automatically stop.
[Analog output
proof test
elapsed time]
(RO)
< 0 – 4,294,967,295 >
(days)
< 0 >
The elapsed time since the last
analog output proof test or since
commissioning if no analog
output proof test has been
executed.
All Outputs
[Safe state
latching
behavior]
< Enabled >
< Disabled >
Defined in
section
7.3.13.1
“Safety Function
Status”.
Behavior of a safe state when
the reason for activation no
longer applies, to either
deactivate when Disabled, or
to remain active (latch) until
power is cycled when Enabled.
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...