COMMISSIONING
218
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Safety Function
Status Code
Safety Shutdown Reason Codes
DATA MEMORY
FAILURE
NOVRAM ENTITY BCC ERROR
The data read from non-volatile memory is corrupted.
NOVRAM READ BACK ERROR
The data written to non-volatile memory did not read back correctly.
NOVRAM CORRUPT
The non-volatile memory is corrupted.
NOVRAM ADMINISTRATION BCC ERROR
The data facilitating access to non-volatile memory is corrupted.
7.3.13.3 Other Errors
There are also other Safety Function Status codes can also cause the
outputs to go to a safe state. These errors are not latchable and the AO
current is fixed.
Safety Function
Status Code
Safety Shutdown Reason Codes
Safety Function
Not Used
This Safety Function selection is available on all three outputs. When
selected, the output is not functional. For the analog output, the output current
becomes fixed at 21 mA.
Analog Output
Mode Disabled
The analog output is not functional, and the output current is fixed at 0 mA.
7.3.13.4 Uncertain Conditions
These are not errors but are considered to be uncertain conditions,
since the requested current level cannot be produced.
Safety Function
Status Code
Safety Shutdown Reason Codes
Analog Output
Over Range
An analog output current level above 20.5 mA is being requested. The actual
current level stays at the upper limit of 20.5 mA and the SIL function health
status becomes Uncertain.
Analog Output
Under Range
An analog output current level below 3.8 mA is requested. The actual current
level stays at the lower limit of 3.8 mA and the SIL function health status
becomes Uncertain.
Analog Output
Zero Span
The Upper Range Value and Lower Range Value are equal, preventing a
product level percent of range from being calculated. The output current stays
at the upper limit of 20.5 mA and the SIL function health status becomes
Uncertain.
Analog Output
Not Calibrated
The analog output has not been calibrated. The output current which
corresponds to the product level may not be accurate.
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...