COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
227
954 SmartServo FlexLine
Name
Value Range
Default Value
Description
[Analog output
safety function]
< Not used >
< Overfill >
< Underfill >
< Overfill and underfill >
< Overfill and
underfill >
The condition of product level
relative to the threshold which
will determine the activation of
an analog output safe state, as
an underfill or overfill condition.
Overfill: activation occurs when
the product level is above the
Overfill Threshold.
Underfill: activation occurs
when the product level is
below the Underfill Threshold.
Overfill and underfill: activation
occurs when the product level
is above the Overfill Threshold
or below the Underfill
Threshold.
Not used: the analog output
remains in high burnout safe
state of 21 mA and does not
perform any function.
[Analog output
overfill
threshold]
< 0 – 3.402823 × 10
38
>
(meters)
< 0 >
The product level limit value
for determining an overfill
condition for the analog output.
[Analog output
underfill
threshold]
< 0 – 3.402823 × 10
38
>
(meters)
< 0 >
The product level limit value
for determining an underfill
condition for the analog output.
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...