COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
141
954 SmartServo FlexLine
7.3.8.4.2 Commissioning Parameters for MPT Temperature Calculations
NOTE: Make sure the RTD/MPT jumper is set to MPT.
☛
The following entities
must
be set set by Engauge or HART
SmartView for a correct functioning of the FII-RTD module in an
instrument. The default values are available after initialization of the
non-volatile memory.
Name
Explanation
Value Range
Default
[Lowest element offset]
The distance from tank zero
till the bottom of the probe
floating point number:
<-x.x .. +x.x>
<80.0>
[Number of elements]
The number of elements
used
<1..6>
<0>
[Element type]
The type (material) of the
used RTDs
<Pt100 large + small>
<Ni191>
<PtCu100>
<Cu100>
<Cu90 enraf + weston/
solartron/nulectrohms>
<Sangamo MRT>
<Sangamo spot>
<No type>
[Measurement type]
Selects RTDs,
MPT
, or
MRT.
<RTD 3wire>
<RTD 4wire>
<MPT>
<MRT>
<No type>
[MPT sensor length]
The length of the MPT
probe
floating point number:
<-x.x .. +x.x>
<80.0>
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...