COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
109
954 SmartServo FlexLine
With the HART protocol, an analog 4-20 mA signal can be combined
with a digital Frequency Shift Keying (FSK) signal. See
Figure 7-10
Figure 7-10
The analog and digital signals within the HART® communication
7.3.7.2 Software Description
The FCI-HT board, being a functional module of the 954 SmartServo
FlexLine, contains embedded software which enables it to collect data
input from sensors via both the HART bus and the FlexConn CAN bus.
Moreover the FCI-HT module can calculate the HIMS
1
product density.
The
main
function of the FCI-HT software is to measure HIMS product
density, by connecting the FCI-HT board via the HART bus to 1 or 2
pressure sensors, and via the FlexConn bus to a product level and a
water level sensor.
To measure product density, the needed standard system configuration
is:
HART pressure sensor P1 (product pressure)
HART pressure sensor P3 (Vapour pressure)
Product level scanned from a FlexConn board (e.g. TII-XR)
Water level scanned from a FlexConn board (e.g. FII-VT)
For tanks that are free venting to the atmosphere or floating-roof tanks,
P3 pressure is not required. The water level sensor is also optional.
1. Hybrid Inventory Measurement System
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...