COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
213
954 SmartServo FlexLine
SIL overfill and underfill protection (FII-SIL)
7.3.12.1 Introduction
Field Interface Instrument - Safety Integrity Level (FII-SIL) is an optional
FlexConn board. The FII-SIL module provides overfill and underfill
protection functionality certified and suitable for use in Safety
Instrumented Systems at SIL 2 with systematic capability at SIL 3. It is
used with the 954 SmartServo FlexLine tank gauge system.
FII-SIL provides two relay contacts for signaling a safety shutdown or
safe state, and one 4-20 mA analog output both for monitoring the
product level and signaling a safe state. The presence of two relay
contacts provides configuration flexibility, such as separate signaling of
overfill and underfill conditions, or the capability of an overfill early
warning to allow corrective action before an overfill condition prompts a
safety shutdown.
The physical contacts of each relay are closed or energized during
normal operation. When a relay is in a safe state, the physical contacts
are open or de-energized. This allows loss of power to also signal a
safe state.
In compliance with NAMUR NE 43, the analog output signals a safe
state when the current at or above 21 mA, or is at or below 3.6 mA.
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...