COMMISSIONING
174
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
7.3.10.5 Configuration of Gauge TRL/2 through Engauge
You must configure the gauge TRL/2 through engauge. Follow the steps
to configure the gauge TRL/2:
1. Connect the HCI TRL/2 card in FlexLine954 gauge.
2. Scan the gauge through SmartLink.
3. In the Engauge tool, right click on HCI-TRL board. Click on
Commis- sioning
4. The TAB sheet
TRL2 Modbus Slave
appears:
5. Under commissioning do the configuration as follows:
a) Enter the Rex Unit ID, DAU Unit ID, Rex Modbus
Address, DAU Modbus Address, GPU instrument
address, FlexConn instrument address.
NOTE: The basic configuration (Rex Unit ID, DAU Unit ID, Rex
Modbus Address, DAU Modbus Address, GPU instrument address,
FlexConn instrument address) of Gauge TRL/2 card must be done
using Engauge tool through SmartLink..
NOTE: The parameter for Rex Unit ID, DAU Unit ID, Rex Modbus
Address, DAU Modbus Address should be entered as per emerson
system, as in saved database (Refer "Saving configuration in
database").
Содержание FlexLine SmartServo 954
Страница 1: ...Service Manual 954 SmartServo FlexLine ...
Страница 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Страница 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Страница 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Страница 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...