101
NTT 240/460
Operation mode
Installation and user guide
Rev: 4.0
6.15.2 Sensored speed control
Operation conditions:
•
control is available with any supported motor type and with any supported feedback (also Hall sensor feedback
is recommended for low performance application only).
•
main speed reference can be analog, inside or frequency reference and fieldbus reference available for any
operation mode.
•
auxiliary speed reference or torque limit reference are available for I/O and Modbus RTU operation mode only.
•
about regulation, speed/current regulators are available.
•
brake motor management is available.
•
trapezoidal ramps and “S”-ramps are available.
During speed control with torque limit, the percentage of set torque is reffered to motor parameter called ‘
Nominal
Current’
.
The following image shows an example of setting of a speed control, with torque limit, working in Modbus RTU
mode, then you can set:
•
the reference type: analog/inside/frequency/tab. selection for I/O and Modbus mode or or fieldbus prameters (in
the case shown in picture, speed and torque reference are analog).
•
full scale for analog analog inputs.
•
optimal PID regulators for application.
•
desired digital I/O.
!
In order to obtain a correct operation, please ensure to perform Factors calculation procedure: please see
.
See
“Ch. 5 Wiring and connections” pag. 26
for more details about connectors:
»
J5-6 connector
: for feedback connection, see:
1.
“6.03.2.e Incremental encoder with/without HALL sensors” pag. 57
2.
“6.03.2.f HALL sensors only” pag. 57
3.
“6.03.2.g SSI absolute encoder” pag. 58
4.
»
J3 and J7-8-9 connector
:
1. provide the main speed reference in the differential input (pins 1-2 of J9) or the frequency reference (pins
1 to 6 of J7) or fill the target speed table-selection. For details about input reference, please see
.
2. provide the auxiliary reference for torque limit control or for second speed reference (pin 3-4 of J9). For
details about input reference, please see
“6.09.2 Auxiliary references” pag. 88
.
3. for fieldbus operation modes, connect J3 connector and see related fieldbus manuals for information about all
control topology parameters.
4. connect the appropriate input and output signals (please see
).