33
NTT 240/460
Wiring and connections
Installation and user guide
Rev: 4.0
5.05 J3 connector: CM option configuration
FIELD BUS
OUT
IN
J3
FIELD BUS
OUT
IN
J3
FIELD BUS
J3
FIELD BUS
OUT
IN
J3
1
2
3
4
5
6
B
A
8
1
8
1
Act
Link/Act
Act
Run
Link/Act
Act
Link/Act
Act
Link/Act
Bus
Failure
B
A
1
8
1
8
B
A
8
1
8
1
Connector TYPE
Double RJ45: IN (A) and OUT (B) parallel connected ports
Utility
Fieldbus comunication protocols:
• Canopen® CiA301e CiA402
• Modbus RTU
N° pins
8 x 2: A1-A8 and B1-B8
(CIA303 st Modbus RTU
standard)
PIN
J3 connector description - CM Option
Cable
A1-B1
CAN H
High Canopen® data
8
1
A2-B2
CAN L
Low Canopen® data
A3-B3
GND
Common Ground for Canopen®
A4-B4
+ data for RS485 Modbus RTU
A5-B5
MODBUS -
- data for RS485 Modbus RTU
A6-B6
-
A7-B7
Shortcircuit
For possible external signal or supply
A8-B8
GND
Common Ground for Modbus RTU
In order to ensure a correct operation for Canopen® Fieldbus comunication, please follow instruction below:
•
connect external 120Ω termination resistor
•
the table below shows Bus total lenght related to Baudrate:
Baudrate
Bus total lenght
1 Mbit/s
< 20m
500 kbit/s
< 100m
250 kbit/s
< 250m
125 kbit/s
< 500m
50 kbit/s
< 1000m
20 kbit/s
< 2500m
10 kbit/s
< 5000m
!
NOTES:
•
Monitored Fieldbus: for information, see
.
•
Keep comunication cables far from supply and feedback cables.
•
It may be necessary to use a repeter or signal amplifier for bus lenght grater than 1000m.
•
Use shielded patch cable (pin-to-pin) FTP 568 (B) Cat. 5 or better.
•
As to connect multiple drives, RJ45 needs a cascade connection, so the wiring between the drives
themselves must be pin-to-pin.
•
Node id address is settable via keybord; please see
“6.06 Display and keyboard” pag. 76
.
•
For information about cable, see