NTT 240/460
Wiring and connections
Installation and user guide
Rev: 4.0
Minimum cable section for motor cable is shown below related to drive power sizes:
Drive Power Size
Minimum Section
mm2 (AWG)
Maximum Section
mm2 (AWG)
NTT 240 1,5/3
4 x 1 mm
2
(AWG17) Shielded
2.5 mm
2
(AWG13)
NTT 240 3/6
4 x 1 mm
2
(AWG17) Shielded
NTT 240 6/12
4 x 1.5 mm
2
(AWG15) Shielded
NTT 240 10/20
4 x 2.5 mm
2
(AWG13) Shielded
NTT 460 1,5/3
4 x 1 mm
2
(AWG17) Shielded
2.5 mm
2
(AWG13)
NTT 460 3/6
4 x 1 mm
2
(AWG17) Shielded
NTT 460 6/12
4 x 1.5 mm
2
(AWG15) Shielded
NTT 460 10/20
4 x 2.5 mm
2
(AWG13) Shielded
6 mm
2
(AWG9)
NTT 460 20/40
4 x 4 mm
2
(AWG11) Shielded
NTT 460 35/70
4 x 6 mm
2
(AWG9) Sh M6x16 exagonal screw
16 mm
2
(AWG5)
NTT 460 45/90 (45/150)
4 x 10 mm
2
(AWG7) Sh M6x16 exagonal screw
NTT 460 75/150
4 x 25 mm
2
(AWG3) Sh M6x16 exagonal screw
25 mm
2
(AWG3)
!
NOTES:
•
It’s mandatory to use shielded cables and to connect shield to PE terminal both drive and motor side.
•
To ensure a correct electric wiring, and for electric safety, use an adequate cap.
•
For cable lenght longer than 50meters, it could be necessary to use a triphase motor choke to grant
drive correct operation.
•
It’s recommended to perform motor autophasing procedure to ensure that connection is correct (it’s
mandatory if third party motor is used). Please see
“6.07 Motor autophasing” pag. 82
•
For information about H.D.T. AC brushless motors wiring (serie B05-B26, BSD10-BSD14 e MS04-MS08),
refer to technical manuals downloaded from internet corporate site: