Operation mode
Installation and user guide
Rev: 4.0
2.
PID speed setting
: parameters to set are K
P
e il K
I
.
•
set K
I
= 0
: integral action erased.
•
increase gradually K
P
until until speed resonance appears
: in this condition an evident speed error
and resonance appear in Scope visualization (besides, this condition leads to a motor unusual noise).
•
halve K
P
value
: halving K
P
, system avoids oscillation in transient conditions..
•
increase gradually K
I
: increase until misured speed variable accurately follows the desired speed
reference. In any case, K
I
parameter should not be greater than
40% of K
P
previously set.
When observing the behavior of the load corresponding to the reference changes, please keep a waveform
responce as possible without overshoot (low gain set), but also with enough performance (high gain set). Therefore
tuning is always the result of compromises between stability and performance.