S5
LIMITS
S.5000
Maximum speed
0 ÷ 20000 RPM
W
S.5001
Maximum current
0.0 ÷ 1000.0 %
W
S.5002
Limit current accu-
racy
‘dEC 0’ without decimal
‘dEC 1’ with 1 decimal
S
S7
FIELDBUS
S70 CHOICE
S.7000
Fieldbus choice
‘0 Io’ Input/Output
‘1 mod’ Modbus
‘2 CAn’ Canopen
‘3 EtH’ Ethercat
‘4 Pnt’ Profinet
‘5 PrF’ Profibus
S
S71 MODBUS
S.7100
MODBUS address
1 ÷ 247
S
S.7101
MODBUS parity
check
‘0 nuL’ null
‘1 EUE’ pari
‘2 odd’ dispari
S
S.7102
MODBUS baudrate
‘9600’ - ‘14400’ - ‘19200’
‘38400’ - ‘57600’ - ‘115200’
S
S.7103
Timeout
10 ÷ 4000 ms
S
S.7104
Timout enable
ON/OFF
S
S72 CANOPEN
S.7200
CANOPEN address
1 ÷ 127
S
S.7201
CANOPEN baudrate
‘10’ - ‘20’ - ‘50’ - ‘100’ - ‘125’
‘250’ - ’500’ - ‘800’ - ‘1000’
S
S.7202
Timeout
10 ÷ 4000 ms
S
S.7203
Timout enable
ON/OFF
S
S73 PROFIBUS
S.7300
PROFIBUS address
1 ÷ 125
S
S74 ETHERCAT
S.7400
ETHERCAT alias
1 ÷ 65535
S
S75 PROFINET
S.7500
192 . 168 . 1 . 10
ADDRESS
Profinet IP address fields
W
S.7501
S.7502
S.7503
S.7510
255 . 255 . 255 . 1
ADDRESS
Profinet Subnet Mask ad-
dress fields
W
S.7511
S.7512
S.7513
S.7520
192 . 168 . 1 . 1
ADDRESS
Profinet Gateway address
fields
W
S.7521
S.7522
S.7523
S8
MOTOR BAKE
S.8000
Enable time
10 ÷ 2000 ms
W
S.8001
Disable time
10 ÷ 2000 ms
W
S.8002
Deceleration ramp
0 ÷ 60000 RPM/s
W
S.8003
Brake enable speed
1 ÷ 500 RPM
W
H6 BRAKING RESISTOR
H.6000 Ohmic value
10 ÷ 10000 Ω
S
H.6001 Power rating
30 ÷10000 W
S
H.6002 Overload time
1 ÷ 255 s
S