If replacing a 115 VAC pump, you can disconnect power at the pump and use it to power the Hub
only. The new variable speed pump however, requires 230 VAC which will have to be run separately.
Refer to the included pump manual for input power wiring.
If using an existing timeclock to power the Omni VS Hub, set it to run constantly. If the VS Omni Hub
will be connected to a panel or switch, the power will have to be left on continuously.
Grounding
Connect a ground wire from the primary electrical panel to the Hub's ground connection as shown in
the previous diagrams. Also ground each piece of high voltage equipment that is connected through
the Hub or Smart Relay.
Variable Speed Pump Input Power
The VS Omni pump requires a constant 230 VAC, 60Hz input power whether from the VS Omni Hub
using the Wiring Whip or directly from a service panel/switch. Refer to the VS Omni Pump manual for
the location of the wiring terminals as well as other related high voltage wiring information.
Connect 115 VAC to Hub
only and run 230 VAC
separately to the new
VSP
Neutral
Disconnect from existing
115 VAC pump
L1
Ground
115 VAC
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS