MAN3186 - TITANUS MICRO
•
SENS®
85
TITANUS MICRO·SENS®
d
A
B
C
D
5.3.1.2 U-pipe system
Image 48:
U-pipe system for room monitoring
Limit values
Min. distance between device and T-piece
2 m
Max. distance between device and T-piece
20 m
Max. branch lengths
25 m
Max. overall pipe length of pipe Ø 25 mm
50 m
Max. overall pipe length with fan voltage 9.0 V; pipe
∅
25 mm
40 m
Min. distance between two aspiration apertures (d)
4 m
Max. distance between two aspiration apertures (d)
10 m
Max. number of aspiration apertures (n)
8 units
Table 25:
Limit values of U-pipe system for single hole monitoring
Number of aspiration apertures
2
4
6
8
Ø aspiration aperture [mm]
1)
A
B
C
D
6.0
-
-
-
4.2
4.4
-
-
3.4
3.6
3.6
-
3.0
3.0
3.2
3.2
Table 26:
Diameter of the aspiration apertures of the U-pipe system for single hole
monitoring
1)
Punching diameter of the aspiration
‑
reducing film sheet