Preparing the functionality
1
TITANUS MICRO·SENS®
2
Test pipe
3
Aspiration aperture Ø 4.6 mm
4
Aspiration aperture Ø 4.2 mm
5
Aspiration aperture Ø 7.0 mm
6
Pressure measurement hose
7
Adapter
8
Digital fine pressure gauge (example)
► Connect the pressure measurement hose of the test pipe to the adapter
(connection B). When performing a limited function check without a
digital fine pressure gauge, the pressure measurement hose connection
must be closed.
► Connect the service PC and TITANUS MICRO·SENS® using the
diagnostic tool.
► Start the diagnostic software.