MAN3186 - TITANUS MICRO
•
SENS®
83
TITANUS MICRO·SENS®
d
A
B
C
D
E
5.3.1.1 I-pipe system
Image 47:
I-pipe system for room monitoring
Limit values
Min. distance between device to first aspiration aperture
2 m
Max. distance between device to first aspiration aperture
20 m
Max. overall pipe length of pipe Ø 25 mm
40 m
Max. overall pipe length with fan voltage 9.0 V; pipe
∅
25 mm
30 m
Min. distance between two aspiration apertures (d)
4 m
Max. distance between two aspiration apertures (d)
10 m
Max. number of aspiration apertures (n)
5 units
Table 22:
Limit values of I-pipe system for single hole monitoring
Number of aspiration
apertures
1
2
3
4
5
Ø aspiration aperture [mm]
1)
A
6.8
4.6
4.0
3.4
3.0
B
-
5.0
4.2
3.6
3.2
C
-
-
4.4
3.8
3.4
D
-
-
-
4.0
3.6
E
-
-
-
-
3.8
Table 23:
Diameter of the aspiration apertures of the I-pipe system for single hole
monitoring
1)
Punching diameter of the aspiration
‑
reducing film sheet