MAN3186 - TITANUS MICRO
•
SENS®
25
1
Pipe system
2
TITANUS MICRO·SENS®
3
Air return
4
Fire alarm cable (FDCP/power supply or to the next unit)
5
Indicator bus*
1
6
Detector box*
1
7
Front film sheet for remote display*
1
8
Remote display*
1
9
Response indicator*
1
10
Diagnostic tool
11
Test pipe*
1
12
Reset and disconnect button*
1
13
Membrane cable entries M20*
1
14
Membrane cable entries M25*
1
15
Network module*
1
16
Reset circuit board*
1
17
Additional housing*
1
18
Relay module RU-1*
1
19
Relay module RU-2*
1
*
1
optional
The components illustrated in the overview can be used optionally.
3.2.2 Device
The TITANUS MICRO·SENS® consists of the following components:
▪ Device base
▪ Detection unit
▪ Pipe system
Device base
▪ Connections for 25 mm aspiration pipe (inlet and return)
▪ Cable glands
▪ Potential-free contacts for connection to an FDCP
Detection unit
▪ Sensitive detection with state-of-the-art technology based on the
scattered light smoke detector principle with integrated air flow
monitoring