MAN3186 - TITANUS MICRO
•
SENS®
86
No standard conformity in case of improper project planning
The air flow monitoring should be set to
≤20 % to achieve project planning
that complies with AS ISO 7240.
NOTE
Number of aspiration apertures
2
4
6
8
1 blocked aspiration aperture
±20%
±10%
-
-
2 blocked aspiration apertures
O
±20%
±15%
±10%
3 blocked aspiration apertures
O
O
±25%
±20%
4 blocked aspiration apertures
O
O
O
±30%
5 blocked aspiration apertures
O
O
O
O
6 blocked aspiration apertures
O
O
O
O
7 blocked aspiration apertures
O
O
O
O
… detected with main air flow set to x%
Table 27:
U-pipe system triggering thresholds
- not possible
O not feasible
Example
If blockage of three aspiration apertures of a total of eight aspiration
apertures should be detected, the air flow monitoring setting must be set to
±20% using the diagnostic tool.