MAN3186 - TITANUS MICRO
•
SENS®
93
d
TITANUS MICRO·SENS®
5.3.2.3 U-pipe system
Image 53:
U-pipe system, e.g. for equipment monitoring
Limit values
Min. distance between device and T-piece
2 m
Max. distance between device and T-piece
20 m
Max. branch lengths
25 m
Max. overall pipe length of pipe Ø 25 mm
50 m
Max. overall pipe length with fan voltage 9.0 V; pipe
∅
25 mm
40 m
Min. distance between two aspiration apertures (d)
0.1 m
Max. distance between two aspiration apertures (d)
4 m
Max. number of aspiration apertures (n) per pipe system
8 units
Table 38:
Limit values of U-pipe system for simplified pipe project planning
Number of aspiration
apertures
2
4
6
8
Ø aspiration aperture
[mm]
1)
6.0
4.2
3.4
3.0
Table 39:
Diameter of the aspiration apertures for the U-pipe system with simplified
project planning
1)
Punching diameter of the aspiration
‑
reducing film sheet