MAN3186 - TITANUS MICRO
•
SENS®
216
► Enter the pre-selection time needed to reach the desired aspiration
aperture and supply it with smoke.
Image 145:
Checking ROOM·IDENT and response indicators
► Press the "Start" button to start the test.
► Make sure that the TITANUS MICRO·SENS® switches from aspiration
mode to purge mode.
► Make sure that the "Measuring active" and "Test mode active" buttons
are illuminated.
► Go to the corresponding aspiration aperture quickly.
► Supply test smoke to the aspiration aperture before the selected
preselection time has elapsed.
► Make sure that the generated trail of smoke is drawn into the aspiration
aperture.
► Wait approx. 5 to 10 seconds before stopping the supply of test smoke.
► Make sure that the TITANUS MICRO·SENS® switches from purge
mode back to aspiration mode after the pre-selection time has elapsed.