5.1.5 Project planning limits
The following limit values must always be observed for the
TITANUS MICRO·SENS®:
▪ The minimum pipe length between two aspiration apertures is 4 m (with
simplified project planning 0.1 m)
▪ The minimum pipe length between two aspiration apertures for localising
the fire site is 3 m.
▪ The maximum pipe length between two aspiration apertures is 10 m.
▪ The maximum monitored surface for each aspiration aperture
corresponds to the monitoring range for a point-type detector in
accordance with the respective national standards.
▪ A maximum of eight aspiration apertures are possible for each
TITANUS MICRO·SENS®.
▪ A maximum of five intake openings are possible for localising the fire
site.
The maximum overall monitoring area and the maximum overall pipe length
depend on the project planning selected.
Max. overall monitoring area
per TITANUS MICRO·SENS®
Max. project planning pipe length
1)
500 m
2
50 m (pipe Ø 25 mm)
Table 11:
Overall monitoring area and pipe length
1)
Depending on the project planning selected, restricted values apply in
some cases.
There may be restrictions due to country-specific regulations which conflict
with the project planning limits stated in this document.