MAN3186 - TITANUS MICRO
•
SENS®
151
1
2
1
3
4
5
6
Missing monitoring for rupture
The capillary hose cannot be monitored for rupture in case of the special
application of ceiling feed-throughts in which the aspiration reducing film
sheets are upstream in T-pieces (pipe hoods).
NOTE
6.18.2 Installation of the ceiling feed-through for special
applications
Image 100:
Ceiling feed-throught with upstream aspiration
‑
reducing film sheet
1
Pipe system
2
T
‑
piece (pipe hood)
3
Aspiration
‑
reducing film sheet
4
Hose nozzle
5
Capillary hose
6
Suspended ceiling
The following work steps are required to install a ceiling feed-through: