No standard conformity in case of wrong energy supply
The energy supply of the TITANUS MICRO·SENS® must be approved in
accordance with AS ISO 7240
‑
4.
NOTE
5.4 Energy supply
When configuring the external energy supply, the alarm-ready state and the
alarm state of the connected devices are taken into account. The state with
the higher current consumption is decisive for selecting the energy supply.
Refer to the chapter "Technical data" for the current consumption values of
the TITANUS MICRO·SENS®.
Alarm state
Alarm current
In the event of an alarm, the energy supply must provide the alarm current
for:
▪ Connected devices
▪ Any connected accessories
=
0
·
_0
+
1
·
_1
+
⋯
+
·
Variable
Unit
Description
A
Alarm current
-
Number of devices
A
Alarm current of device
-
Number of accessories 1
A
Alarm current/current consumption of accessories 1
-
Number of accessories i
A
Alarm current/current consumption of accessories i
_