background image

 

 

VSL3.928.010SIASY

 

 

1

 

1. 

Feature 

 

Used as an warning device to generate fire alarm;   

 

Installation and wiring same as detector base;   

 

Driven  by  detection  circuit,  no  need  for  extra 
power line.

 

2. 

Description 

VG-6611S  Conventional  Alert  Base  is  designed  for  the  application  inside  a  closed  room.  As  an 

warning  device,  the  base  will  generate  alarm  sound  when  the  detector  detects  a  fire  occurred. 

Installed as a base, it is compatible with the range of conventional detectors. It is usually installed in 

hotel  room,  residential  bedroom  or  other  locations  that  are  far  away  from  the  audible  and  visual 

alarm. 

3. 

Technical Data   

Operating voltage: 

15VDC

28VDC 

Operating current: 

Standby current: 0mA 

Action current: ≤ 4mA (12V) 

Sound level 

>75dB at 1 meter 

Tonal modification cycle 

0.6~1.5S 

Environment 

Temperature:

-10

~+55

 

Relative humidity≤95%

non-condensing 

Weight 

67g 

Dimension 

diameter of 102mm, height of 25.5mm 

Installation hole distance 

73mm 

4. 

Outline and Installation Dimension 

 

5. 

Installation and Wiring 

1) 

The  flame  resistant  twisted-pair  ZR-RVS-2×1.0~1.5mm

2

  is  recommended  to  be  used  for  the 

wiring. 

2) 

Before the installation, please check whether the shell is intact without any damage, and whether 

the label is complete. 

3) 

The terminals of the alert base shall be connected as the following diagram: 

Control panel terminal Zone Input+: connected with the alert base’s position “1” or “2”; 

Control panel terminal Zone Input

-

: connected with alert base’s position “4”;

 

VG

-

6611S Conventional Alert Base   

 

Base

 

 

 

Installation and Operation Manual V1.00

 

 

Отзывы: