MAN3186 - TITANUS MICRO
•
SENS®
49
1
2
3
5
4
3.3.5 Air filter and special filter
Image 29:
Air and special filter
1
TITANUS MICRO·SENS®
2
Special filter SF-650
3
Air filter LF-AD-x
4
Special filter SF-400
5
Direction of flow
In monitoring areas with disturbing ambient influences (e.g. dust), an air or
special filter is to be used to protect the TITANUS MICRO·SENS®.
Air filter type LF-AD-x
Air filter type LF-AD-x, consisting of a plastic housing with two pipe
connections and filter elements, is used as a standard air filter. The air filter
is automatically monitored for dirt (blockage) by the air flow monitoring of the
TITANUS MICRO·SENS®. If air filters are soiled, the filter elements can
simply be replaced after opening the filter housing.
Type
Application
Examples
LF
‑
AD
Coarse filter for separating
particles > approx. 15 µm
Dust, insects, fibres,
hairs, cinders, pollen
LF
‑
AD
‑
1
Filter for separating
particles > approx. 10 µm
As above, additionally:
Colour pigments and fine dust
LF
‑
AD
‑
2
Fine filter for separating
particles > approx. 5 µm
As above, additionally: Fine dust
in lower concentrations
Table 4:
Overview of the air filters