MAN3186 - TITANUS MICRO
•
SENS®
59
Temperature range
Humidity
Fan
Displays on the device
1)
optional
Infrared interface
Connections
Response sensitivity
4.2 Accessories
▪ Detector box TITANUS MICRO·SENS®
▪ Remote display
▪ Response indicator
▪ Relay module
▪ Reset circuit board
▪ Network module
[°C]
-
20 … +60
Deep freeze version [°C]
-
40 … +60
Non-condensing [% RH]
Max. 95 (non-condensing)
Design
Axial
Fan service life (12 V)
60,000 h at 24 °C
Operation
Green LED
Alarm
Red LED
Pre-alarm
1)
Red LED
Collective fault
Yellow LED
Bar graph
1)
Smoke level 1
… 10 (10x yellow LED)
Alarm location display
1)
5x red LED
IR transmitter/receiver
Terminal connections [mm²]
0.5
… 2.5
Fire alarm cable
shielded (e.g. type J-Y(ST)Y)
Cable glands
8x M20, 6x M25
Pipe connections (conical)
Ø 25 mm, 1x for aspiration pipe, 1x air return
Detection unit
DM-TMx-xx-10-x [% light obscuration/
m]
0.1
… 2.0
DM-TMx-xx-50-x [% light obscuration/
m]
0.5
… 2.0