MAN3186 - TITANUS MICRO
•
SENS®
212
1
2
3
4
7
6
5
8.8 Replacing the filter elements of special
filter type SF-400 / 650
Removing the special filter leads to an air flow fault on the
TITANUS MICRO·SENS®.
Image 143:
Replacing the filter elements of the special filter
1
Pipe system
2
Special filter type SF
‑
400, SF
‑
650
3
PVC transition screw connections
4
TITANUS MICRO·SENS®
5
Screw-in plugs
6
Filter element
7
Filter housing
► Loosen the two PVC transition screw connections on the special filter.
► Remove the special filter from the pipe system.
► Loosen one of the two screw-in plugs on the filter housing.
► Remove the filter element.
► Insert the new filter element into the filter housing.
► Screw the screw-in plug into the filter housing.
► Re-insert the special filter into the pipe system. Observe the flow
direction that is specified on the type plate of the filter housing.