168
Risk of injury due to flammable liquids and vapours
Formation of explosive/highly flammable vapour/air mixtures is possible.
Injuries to health due to direct or indirect contact.
► Prior to processing, observe the safety notes of the manufacturer.
WARNING
6.25 Installation of test adapter
A test adapter must be installed upstream of the air inlet of a
TITANUS MICRO·SENS®.
The test adapter must always be closed in normal operation and is only
opened for maintenance and service purposes, to introduce test gas or
smoke aerosols.
Image 116:
Installing the test adapter
► Before gluing into place, free the cut edges from dirt and grease with
Tangit cleaner.
► Glue the test adapter in the pipe system in the immediate proximity of
the device with Tangit glue.