MAN3186 - TITANUS MICRO
•
SENS®
112
6.3 Installation of device
Image 67:
Mounting orientation
1
Aspiration pipe
2
Angled pipe
3
Air return
4
TITANUS MICRO·SENS® with top air outlet
5
TITANUS MICRO·SENS® with bottom air outlet
The device can be installed with the air inlet pointing up or down. Rotate the
cover accordingly by 180°.
Bottom air outlet
Make sure that air outlet of the device is not obstructed. Maintain a distance
of at least 10 cm between the air outlet and surrounding components (e.g.
wall projection).
Air outlet pointing up
Make sure that no foreign particles and no dripping water can enter the air
outlet opening. Use a short pipe angled down for this.
The device can be installed with the air intake pointing up or down. Rotate
the detection unit accordingly by 180°.
1
2
3
4
3
5
1
m
in
.
1
0
mm
m
in
.
10
mm