Danger of device damage due to electrostatic discharge
Only perform the following work with the device disconnected from the
mains. Do not touch the components of the circuit boards without an anti-
static set.
NOTE
6 Installation
You will find information about installing the TITANUS MICRO·SENS® and
the pipe system in this chapter.
6.1 General information
The provisions, guidelines and terms listed in the chapter "Project planning"
apply.
The following must be observed when installing the
TITANUS MICRO·SENS®:
▪ Interventions, changes and modifications to equipment must be avoided.
If adjustments are required, these must be arranged with the operating
company, device manufacturer and/or supply company (written
approval).
▪ All interventions in the house mains (230 V / 400 V supply) and third-
party systems must be carried out on-site. This includes, for example:
– The primary connections of the power supply units
– Any connection to third-party systems (e.g. control panels)
– Carrying out any potentially required lightning and surge protection
measures according to the relevant standards.