Group 1: Inputs
• start/stop, terminals 2 and 3
• digital input, terminals 1 and 9
• setpoint input, terminals 4, 5 and 6
• sensor input, terminals 7 and 8
• GENIbus, terminals B, Y and A
All inputs (group 1) are internally separated from the mains-
conducting parts by reinforced insulation and galvanically
separated from other circuits.
All control terminals are supplied with protective extra-low
voltage (PELV), thus ensuring protection against electric
shock.
Group 2: Output
(relay signal, terminals NC, C, NO)
The output (group 2) is galvanically separated from other
circuits. Therefore, the supply voltage or protective extra-low
voltage can be connected to the output as desired.
Group 3: Mains supply
(terminals L1, L2, L3)
Group 4: Communication cable
(8-pin male socket) - only
TPED
The communication cable is connected to the socket in group
4. The cable ensures communication between the two pumps,
whether one or two pressure sensors are connected. See
section
5.7 Communication cable for TPED pumps
The selector switch in group 4 enables changeover between
the operating modes "alternating operation" and "standby
operation". See the description in section
Fig. 14
Connection terminals TPE Series 2000
Fig. 15
Connection terminals TPED Series 2000
A galvanic separation must fulfil the requirements for reinforced
insulation including creepage distances and clearances specified
in EN 61800-5-1.
TM
03
86
08
20
07
1: Digital input
9: GND (frame)
8: +24 V
7: Sensor input
B: RS-485B
Y: Screen
A: RS-485A
6: GND (frame)
5: +10 V
4: Setpoint input
3: GND (frame)
2: Start/stop
Group
1
Group 2
Group
3
TM
03
91
34
34
07
Group 4
Group 2
Group 3
1: Digital input
9: GND (frame)
8: +24 V
7: Sensor input
B: RS-485B
Y: Screen
A: RS-485A
6: GND (frame)
5: +10 V
4: Setpoint input
3: GND (frame)
2: Start/stop
Grou
p 1