9.2.7 Lubrication status of motor bearings (only 11-22 kW)
This display shows how many times the motor bearings have
been relubricated and when to replace the motor bearings.
When the motor bearings have been relubricated, confirm this
action in the INSTALLATION menu. See section
relubrication/replacement of motor bearings (only three-phase
pumps)
. When relubrication is confirmed, the figure in the above
display will be increased by one.
9.2.8 Time till relubrication of motor bearings (only 11-22 kW)
This display shows when to relubricate the motor bearings. The
controller monitors the operating pattern of the pump and
calculates the period between bearing relubrications. If the
operating pattern changes, the calculated time till relubrication
may change as well.
The displayable values are these:
• in 2 years
• in 1 year
• in 6 months
• in 3 months
• in 1 month
• in 1 week
• Now!
9.2.9 Time till replacement of motor bearings (only three-
phase pumps)
When the motor bearings have been relubricated, a prescribed
number of times stored in the controller, the display in section
9.2.8 Time till relubrication of motor bearings (only 11-22 kW)
will
be replaced by the display below.
This display shows when to replace the motor bearings. The
controller monitors the operating pattern of the pump and
calculates the period between bearing replacements.
The displayable values are these:
• in 2 years
• in 1 year
• in 6 months
• in 3 months
• in 1 month
• in 1 week
• Now!
9.3 Menu INSTALLATION
9.3.1 Control mode
Select one of the following control modes (see fig.
•
Prop. pressure
(proportional pressure)
• Const. pressure (constant pressure)
• Const. curve (constant curve).
How to set the desired performance, see section
9.3.2 External setpoint
The input for external setpoint signal can be set to different signal
types.
Select one of the following types:
• 0-10 V
• 0-20 mA
• 4-20 mA
•
Not active
.
If "Not active" is selected, the setpoint set by means of the R100
or on the control panel will apply.
If one of the signal types is selected, the actual setpoint is
influenced by the signal connected to the external setpoint input.
See section
.
9.3.3 Signal relay
Pumps up to 7.5 kW have one signal relay. The factory setting of
the relay will be Fault.
Pumps of 11-22 kW have two signal relays. Signal relay 1 is
factory-set to Alarm and signal relay 2 to Warning.
In one of the displays below, select in which operating situation
the signal relay should be activated.
For further information, see section
16. Indicator lights and signal
Note
If the pump is connected to a bus, the control mode
cannot be selected via the R100. See section
.
Up to 7.5 kW
• Ready
•
Fault
• Operation
• Pump running (only three-phase pumps up to 7.5 kW)
• Warning (only three-phase pumps up to 7.5 kW).