22. Technical data - three-phase pumps, 11-22
kW
22.1 Supply voltage
3 x 380-480 V - 10 %/+ 10 %, 50/60 Hz - 3 %/+ 3 %, PE.
Recommended fuse sizes
Standard as well as quick-blow or slow-blow fuses may be used.
22.2 Overload protection
The overload protection of the E-motor has the same
characteristic as an ordinary motor protector. As an example, the
E-motor can stand an overload of 110 % of I
nom
for 1 min.
22.3 Leakage current
The earth leakage current is greater than 10 mA.
The leakage currents are measured in accordance with EN
61800-5-1.
22.4 Inputs/output
Start/stop
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Digital
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Setpoint signals
• Potentiometer
0-10 VDC, 10 k
Ω
(via internal voltage supply).
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 100 m.
• Voltage signal
0-10 VDC, R
i
> 50 k
Ω
.
Tolerance: + 0 %/- 3 % at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 500 m.
• Current signal
DC 0-20 mA/4-20 mA, R
i
= 250
Ω
.
Tolerance: + 0 %/- 3 % at maximum current signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 500 m.
Signal relay output
Potential-free changeover contact.
Maximum contact load: 250 VAC, 2 A, cos
φ
0.3 - 1.
Minimum contact load: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
/ 28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos bus protocol, GENIbus protocol, RS-485.
Screened 3-core cable: 0.2 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 500 m.
23. Other technical data
EMC (electromagnetic compatibility to EN 61800-3)
Contact Grundfos for further information.
Motor size [kW]
Max. [A]
2-pole
4-pole
11
11
32
15
15
36
18.5
18.5
43
22
22
51
Motor [kW]
Emission/immunity
2-pole
4-pole
-
0.12
Emission
Motors may be installed in residential
areas (first environment), unrestricted
distribution, corresponding to CISPR11,
group 1, class B.
Immunity
Motors fulfil the requirements for both
the first and second environment.
0.18
0.18
0.25
0.25
0.37
0.37
0.55
0.55
0.75
0.75
1.1
1.1
1.5
1.5
2.2
2.2
3.0
3.0
4.0
4.0
5.5
-
7.5
-
-
5.5
Emission
The motors are category C3,
corresponding to CISPR11, group 2,
class A, and may be installed in
industrial areas (second environment).
If equipped with an external Grundfos
EMC filter, the motors are category C2,
corresponding to CISPR11, group 1,
class A, and may be installed in
residential areas (first environment).
-
7.5
11
11
15
15
18.5
18.5
22
-
Warning
When the motors are
installed in residential areas,
supplementary measures
may be required as the
motors may cause radio
interference.
Motor sizes 11, 18.5 and 22 kW comply with EN
61000-3-12 provided that the short-circuit power at
the interface point between the user's electrical
installation and the public power supply network is
greater than or equal to the values stated below.
It is the responsibility of the installer or user to
ensure, by consultation with the power supply
network operator, if necessary, that the motor is
connected to a power supply with a short-circuit
power greater than or equal to these values:
Motor size
[kW]
Short-circuit power
[kVA]
11
1500
15
-
18.5
2700
22
3000
Note
15 kW motors do not comply with EN
61000-3-12.
By installing an appropriate harmonic filter between
the motor and the power supply, the harmonic
current content will be reduced. In this way the 15
kW motor will comply with EN 61000-3-12.
Immunity
The motors fulfil the requirements for both the first
and second environment.