13. External setpoint signal
The setpoint can be remote-set by connecting an analogue signal
transmitter to the input for the setpoint signal (terminal 4).
Fig. 37
Actual setpoint as a product (multiplied value) of
setpoint and external setpoint
Select the actual external signal, 0-10 V, 0-20 mA, 4-20 mA, via
the R100. See section
Control mode controlled
If control mode controlled, see control hierarchy in section
, is selected by means of the R100, the
pump can be controlled to:
• proportional pressure
• constant pressure.
In control mode proportional pressure, the setpoint can be set
externally within the range from 25 % of maximum head to the
setpoint set on the pump or by means of the R100. See fig.
Fig. 38
Relation between the actual setpoint and the external
setpoint signal in control mode proportional pressure
Example:
At a maximum head of 12 metres, a setpoint of 6
metres and an external setpoint of 40 %, the actual setpoint will
be as follows:
H
actual
= (H
set
- 1/4 H
max.
) x %
external setpoint
+ 1/4 H
max.
= (6 - 12/4) x 40 % + 12/4
= 4.2 metres
In control mode constant pressure, the setpoint can be set
externally within the range from 12.5 % of maximum head to the
setpoint set on the pump or by means of the R100. See fig.
Fig. 39
Relation between the actual setpoint and the external
setpoint signal in control mode constant pressure
Example:
At a maximum head of 12 metres, a setpoint of 6
metres and an external setpoint of 80 %, the actual setpoint will
be as follows:
H
actual
= (H
set
- 1/8 H
max.
) x %
external setpoint
+ 1/8 H
max.
= (6 - 12/8) x 80 % + 12/8
= 5.1 metres
Control mode uncontrolled
If control mode uncontrolled, see control hierarchy in section
, is selected by means of the R100, the
pump is controlled to a constant curve and can be controlled by
any (external) controller.
In control mode constant curve, the setpoint can be set externally
within the range from the min. curve to the setpoint set on the
pump or by means of the R100. See fig.
Fig. 40
Relation between the actual setpoint and the external
setpoint signal in control mode constant curve
14. Bus signal
The pump supports serial communication via an RS-485 input.
The communication is carried out according to the Grundfos bus
protocol, GENIbus protocol, and enables connection to a building
management system or another external control system.
Operating parameters, such as setpoint, operating mode, etc. can
be remote-set via the bus signal. At the same time, the pump can
provide status information about important parameters, such as
actual value of control parameter, input power, fault indications,
etc.
Contact Grundfos for further details.
15. Other bus standards
Grundfos offers various bus solutions with communication
according to other standards.
Contact Grundfos for further details.
T
M
03
86
01
20
07
TM0
2
898
8
1
3
0
4
TM
02 898
8 130
4
Setpoint
External setpoint
Actual setpoint
0
10 V
0
20 mA
4
20 mA
Actual setpoint
90 % of maximum head
Setpoint set by means of
control panel, R100 or PC Tool
E-products
25 % of maximum head
External setpoint signal
Actual
setpoint
[m]
0
10 V
0
20 mA
4
20 mA
Actual setpoint
Maximum head
Setpoint set by means of
control panel, R100 or PC Tool
E-products
12.5 % of maximum head
External setpoint signal
Actual
setpoint
[m]
TM
02
89
88
13
04
Note
If a bus signal is used, the number of settings
available via the R100 will be reduced.
0
10 V
0
20 mA
4
20 mA
Actual setpoint
Max. curve
Setpoint set by means of
control panel, R100 or PC Tool
E-products
Min. curve
External setpoint signal
Actual
setpoint
[%]