Appendix D - ADM Error Codes
88
3A2797ZAA
WMC1 Blue Inline
Con. Fault
WMC2 Red Hose
Con. Fault
WMC3 Red Inline
Con. Fault
WMC4 Blue Hose
Con. Fault
WMC5 Blue Tank
Con. Fault
WMC6 Red Tank
Con. Fault
Unexpected current to relay 1 Alarm
Shorted module
If temperature is being affected by a zone that has
been disabled, replace heat module
WMC7 Red Chiller
Con. Fault
WMC8 Blue Chiller
Con. Fault
WMH1
Motor
Controller
Fault
A general fault has occurred
within the MCM
Deviation Internal hardware failure Cycle power, if the error persists the MCM will need
to be replaced
W0U0 USB Update
Failed
The ADM tried to upload a
system settings file but failed Alarm
System Settings file is
corrupt
Replace the system settings file with a backup or new
file
WSC0
Invalid
Setpoint
Request
The requested controlling
value (pressure or flow) is
outside the limits of the
system
Deviation
System incorrectly setup
On the ADM go into the setup screens -> System->
and ensure that all pages have properly defined
values
Shot incorrectly defined Redefine shot with control parameters within the
limits of the system
Invalid Gel
Timer
Definition
The shot that was entered for
the gel timer is not a valid
shot. This must be fixed before
the gel timer will function
properly
Deviation
Gel timer shot is below
the minimum dispense
amount or set for a
invalid pressure/flow
Select a different shot or modify existing shot data
The MCM has
determined that the gel
timer shot will not be
able to be executed
based parameters
entered in the ADM
If you are certain that the shot is within parameters,
try running the Learn Mode routine found in the setup
screen Calibration. If the error persists, a gel shot
with reduced control parameters is required.
Error
Code Error Name Error Description
Error
Type
Cause
Solution