Appendix B - ADM Setup Screens Overview
62
3A2797ZAA
Supply Screen
This screen allows the user to specify the operating
parameters for off-board, integrated tanks and indicate
which positions have level sensors installed. See the
Tank Feed Systems manual for information about
installing level sensors, see
page 3. The user may select from the following refill
settings: Disabled, Monitor, Manual, Auto Top-Off, Auto
Full-Volume.
NOTE:
Use the “Disabled” setting if off-board tanks are
not installed.
The following describes system operation when each
tank mode is selected.
•
Disabled
• Disables tank operation
•
Monitor (2 Sensors)
• The top sensor generates a high level deviation
and the bottom sensor generates a low level
alarm
• Refill is not supported, no button is provided on
the run screens to initiate refill
• Errors will clear when the corresponding
condition clears
•
Manual (2 Sensors)
• The top sensor generates a high level deviation
and the bottom sensor generates a low level
alarm
• A button is provided to the user on the run
screens to initiate a manual refill operation at
any time
• Manual refill will run until either the high level
sensor sees material, the user aborts the refill
via the refill button on the run screens, or the
refill time-out expires
• The low level alarm will clear when the
condition clears
•
Monitor (3 Sensors)
• Same as
Monitor (2 Sensors)
section, except
that a filled condition is considered as material
filled up to the second or middle sensor
•
Manual (3 Sensors)
• Same as
Manual (2 Sensors)
section, except
that a filled condition is considered as material
filled up to the second or middle sensor. Refill
operations will fill to middle sensor, and
material reaching the top or third sensor is
considered a high level deviation
•
Auto Top-Off (2 or 3 Sensors)
• The low level sensor will generate a low level
alarm
•
Two level sensors installed
: When the high level
sensor does not see material, automatic refill
will begin and continue until either the high level
sensor sees material or until the refill time-out
expires
•
Three level sensors installe
d: When the middle
level sensor does not see material, automatic
refill will begin and continue until either the
middle level sensor sees material or until the
refill time-out expires
• The low level alarm will clear when the
condition clears
• A button is provided to the user on the run
screens to initiate an automatic refill operation
at any time, this button can also be used to
abort a refill operation
•
Auto Full-Volume (2 Sensors)
• The low level sensor will initiate an automatic
refill when it does not see material
• Automatic refill will continue until either the high
level sensor sees material or until the refill
time-out expires
• The low level alarm will clear when the
condition clears
• A button is provided to the user on the run
screens to initiate an automatic refill operation
at any time, this button can also be used to
abort a refill operation
•
Report Red (or Blue) High level in bit 2
• If active (checked ) the HFR (or NVH) will report
a full tank high level condition (top sensor
detects material) as a 7, rather than 3 (bit 2 set
rather than cleared) over the field bus
automation interface.
Refill Setting